Price: US$ 13.90/kg
BW 2 Part Brass Cable Glands

High-Performance and Easy Installation

BW 2 Part Brass Cable Glands

Engineered to deliver unmatched reliability, our BW Brass Cable Glands are manufactured in compliance with BS 6121 Part 1, making them ideally suited for single wire armoured (SWA) cables with plastic or elastomer (rubber) sheathing. Designed specifically for dry indoor environments, these glands ensure secure cable termination with a focus on safety, durability, and ease of use.

Product Range

These glands feature a two-part construction with no loose components, allowing for quick and efficient installation, reducing assembly time and labour costs. Optional integral earth facility enhances grounding performance, while the robust brass construction ensures excellent mechanical strength and corrosion resistance. A preferred choice across industrial and commercial applications, BW Brass Cable Glands combine practicality with premium quality.

Specification

Gland Size:

20mm to 75mm (S & L)

IP Rating:

IP 54

Brass Nuts & Fasteners 01-l1

Technical FAQ – BW 2 Part Brass Cable Glands

Which material should be specified?

Specify the brass alloy and finish on the order. CW614N (CuZn39Pb3) and CW617N (CuZn40Pb2) are different alloys and should not be treated as interchangeable. Confirm the body, seal and any armour-clamping materials for the selected gland.

How do I confirm connection compatibility?

Match the enclosure entry thread, pitch and engagement length. Metric, PG, NPT and BSP are different thread systems; a nominal size does not make them interchangeable. Confirm the actual thread offered for the selected model. IEC 62444 describes cable-gland requirements, not a thread profile.

What dimensions are needed for selection?

Provide the cable construction, outer sheath diameter, bedding diameter and armour dimensions where applicable, together with the enclosure entry. Select from the model’s documented cable acceptance range; entry size is not the cable diameter.

What determines suitability and operating limits?

BW glands are generally used for terminating armoured cable in dry indoor conditions. Do not infer an outdoor weather seal from the BW designation or from armour clamping alone. Confirm the selected product’s documented sealing arrangement and any claimed ingress-protection rating.

What finish and inspection documentation should I request?

State the required surface finish, coating thickness where relevant, and critical dimensions on the order. Material certificates, dimensional reports and any specified performance tests should be agreed in the quotation. A reference to a standard is not a declaration of third-party certification.

Can I request a custom part or export quotation?

Send a drawing or clearly dimensioned sample specification, material, quantity and delivery destination. Identify application conditions and required approvals. Brass Parts India can review the requirement and confirm feasibility, price, documentation and lead time for the quoted part.